Instrument knowledge|Precautions for installation of electromagnetic flowmeter

 

Electromagnetic flow meters can measure conductive liquids and are widely used in chemical, chemical fiber, food, paper, sugar, mining and metallurgy, urban water supply and drainage, environmental protection, water conservancy, steel, petroleum, pharmaceuticals and other industrial fields to measure various acids , Alkali, salt solution, mud, mineral pulp, paper pulp, coal water slurry, corn steep liquor, fiber pulp, grain pulp, lime milk, sewage, etc.。

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

Electromagnetic flowmeter has a series of excellent characteristics, which can solve the problems that other flowmeters are not easy to use, such as the measurement of dirty flow and corrosive flow.

 

Advantage

The measurement channel is a smooth straight pipe, which will not be blocked, and is suitable for measuring liquid-solid two-phase fluids containing solid particles, such as pulp, mud, sewage, etc.;

The detection will not cause pressure loss, and the energy saving effect is good;

The measured volume flow is actually not significantly affected by changes in fluid density, viscosity, temperature, pressure and conductivity;

Wide range of turndown ratio and wide caliber range;

Corrosive fluids can be used.

 

Disadvantage

Cannot be used to measure gas, steam and liquids containing a large amount of gas;

It cannot be used to measure liquid media with very low conductivity, and the electromagnetic flowmeter cannot measure petroleum products or organic solvents and other media;

It cannot be used to measure high temperature media. At present, it is restricted by the lining material and electrical insulation material of the measuring tube of the electromagnetic flowmeter for general industry;

Electromagnetic flowmeters are easily affected by external electromagnetic interference.

 

Installation Precautions

In order to make the electromagnetic flowmeter meet the working conditions of the measurement site and meet the accuracy and function requirements of the instrument, the following precautions are required during the installation process:


1. Install according to the calibration direction

The direction of the arrow on the sensor must be consistent with the actual flow direction. (If the installation is reversed, the flow direction item in the converter menu must be corrected)


2. Ensure that the full pipe is installed

The full tube measurement state must be ensured, and the non-full tube state cannot occur.

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

Avoid installation upstream of the downward pipeline;

Avoid installing at the highest point of the pipeline, which is easy to collect bubbles;

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

When installing on a horizontal pipeline, the two measuring electrodes should not be directly above and directly below the pipeline. When installed vertically, the fluid should flow from bottom to top.

 

3.Straight pipe distance requirements

Must ensure that the first 10 and rear 5 straight pipe sections.

Instrument knowledge|Precautions for installation of electromagnetic flowmeter


4.Series and parallel installation

If several sensors need to be connected in series on the same pipe in sequence, the distance between each sensor should be at least the length of 2 sensors. If two or more sensors are installed parallel to each other, the distance between the sensors must be greater than 1m.

5. installation and bypass pipe

The pipeline where the flowmeter is installed should have a valve that can cut off the medium in the pipeline to facilitate daily maintenance and maintenance. When the process does not allow flow interruption. A bypass pipe can be added to the pipe where the flowmeter is installed.

6.Sensor ground

The sensor must be well grounded separately


Grounding meaning:

Give the signal source a reference to zero potential, so that the measured medium is connected to the earth. The safety requirements (such as lightning strikes) are against external interference. The grounding point is as close as possible to the sensor, and it must not be connected to the grounding point of other equipment. Ground resistance ≤10Ω

 

Grounding requirements:

Electromagnetic flowmeter transmitter housing, shielded wire, measuring conduit and pipes at both ends of the transmitter must be grounded and set a separate grounding point, and must not be connected to public ground wires or upper and lower pipes such as electric motors; the converter part has passed the cable Line grounding, there is no need to ground again to avoid interference due to different potentials.

 

Grounding method with grounding ring:

If the process pipeline is made of insulating material, it must be equipped with a grounding ring to stabilize the boundary conditions. Improve the measurement qualitative and accuracy.

 

7.Ensure that the split type electromagnetic flowmeter is matched and installed

The split type electromagnetic flowmeter should ensure that the electromagnetic flow converter and the sensor are matched with the number, and the number of the converter and the matching sensor is the same (Zhang Guan Li Dai will not work normally)


8. Wire and lay cables correctly

Must be wired and cabled correctly. The connecting cables of the sensor and the converter must be seated in correct numbers and connected correctly (understand the meaning of each line number)

 

Cable installation precautions: The signal cable and the excitation cable are separated through pipes (iron pipes) to prevent interference and mechanical damage. The special cable provided by the company must be used. The signal cable, excitation cable and power line must be installed separately, and the pulse output line should be considered between the lines. Distributed capacitance should not be too long.

 

9 .Reasonable configuration of the rear position instrument

The rear instrument of the electromagnetic flowmeter must be reasonably configured

The active or passive output should be determined according to the requirements of the subsequent instrument. The external power supply for passive output should meet the technical specifications. If the resistance is connected in series, the resistance value should be within the allowable range.

 

10 .proofreading the power supply voltage

The power supply voltage must be calibrated before commissioning (the phenomenon of 24VDC instrument being burned out by 220VAC power supply is endless)

During debugging, only zero position adjustment is allowed, and various parameters are set after factory calibration without any need to change.

 


Share to
RELATED NEWS / News More
  • Number of clicks: 369
    2021 - 07 - 27
    Radar level transmitter are currently widely used in the monitoring of solids, dust particles, liquids, slurries, river water levels, etc. The level signal detected by the radar level transmitter is ultimately connected to the back of our automation control equipment or to the secondary display meter for monitoring control. The specific power supply and communication methods are as follows:1. (4 ~ 20) mA / 24V DC / HART two-wire system2. (4 ~ 20) mA / 24V DC / HART four-wire system3. (4 ~ 20) mA / (85~ 265) V AC / HART four-wire system4. RS485/Modbus/( 6~26)V DC5. Radio frequency 433MThe customer can select the power supply and communication mode according to the actual requirements of the site. If you have any questions, please contact us directly.Xi’an Dechuang Electrical ...
  • Number of clicks: 360
    2021 - 07 - 07
    The screw connection is a widely used detachable fixed connection, which has the advantages of simple structure, reliable connection, and convenient assembly and disassembly. Thread is a key part of thread coupling and screw drive, let us take a look at the classification of thread.According to the tooth shape, it can be divided into triangle, trapezoid, rectangle, zigzag and arc thread;According to the thread rotation direction, it can be divided into left-handed and right-handed;According to the number of spiral lines, it can be divided into single line and multi-line;According to the shape of the thread matrix, it can be divided into cylinder and cone.For threaded connections of radar level transmitters, there are two most common types: G 1 1 / 2A thread; NPT thread.
  • Number of clicks: 321
    2021 - 06 - 29
    The 120GHz FMCW radar level meter successfully applied to the measurement of Chlorinated paraffin in a chemical plant.The working condition is more complicated, the surface foam thickness is about 80cm, the 120GHz radar level meter signal is relatively strong, penetrates the foam, and accurately measures the liquid level.The Main Feature of 120GHz FMCW Radar level meter:1. Not be affected by atmospheric precipitation;2. The ambient temperature is -60°C;3. Being Installed on the outside of tank;4. The antenna inside of the level transmitter is protected by fluoro plastic lens heating;5. The measuring radiation is narrow, easy to install and measurement sensibility;6. The accuracy of the level measurement can't be limited by the temperature of tank;7. Evaporation, Foa...
  • Number of clicks: 0
    2021 - 06 - 25
    Case application I The anti-corrosion radar level meter DCRD1000A5&DCRD1000C5 was successfully applied to a chemical project in Inner Mongolia Since Acid-base solutions are extremely corrosive in industrial production measurement applications, the wetted materials of equipment must be anti-corrosion materials. Our high-frequency radar level meter DCRD1000A5 and guided wave radar level gauge DCRD1000C5 are special models for corrosive conditions. Radar antennas are made of PTFE with good anti-corrosion performance, which has good sealing performance, strong corrosion resistance and stable measurement results.Any inquiry about the radar level meter, welcome to contact us at any time.
  • Number of clicks: 252
    2021 - 06 - 22
    The  Features of DCRD1000C series of Guided Wave Radar Level meter (GWR)The guided wave radar level meter is an excellent level meter with advanced technology, excellent workmanship and high precision. When the guided wave radar level meter is working, an electromagnetic pulse signal is emitted, which is transmitted to the liquid level and returned at a constant speed through a probe or a steel cable, thereby simply and accurately calculating the liquid level height.Guided wave radar level meter are currently used in a wide variety of tank containers. It is used to measure the liquid level or level of medium such as aqueous medium, acidic medium, alkaline medium, oil medium, and particles.The guided wave radar level meter (DCRD1000C series) independently developed by Xi'an Dechuan...
Email:sales@dechuang-auto.com
Adress:
Tel:86-29 88606479
Fax: 86-29 88385903
B203, Gazelle Valley, No.69 Jinye Rd, Hi-tech zone, Xi'an, Shaanxi Province, P.R.China. 710077
Copyright ©2018 - 2019 Dechuang Electrical Technology Co., Ltd SITEMAP
Rhino Cloud Provides Enterprise Cloud Services
犀牛云提供云计算服务