Instrument knowledge|Precautions for installation of electromagnetic flowmeter

DATE: 2020-08-06
BROWSE TIMES: 5

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

 

Electromagnetic flow meters can measure conductive liquids and are widely used in chemical, chemical fiber, food, paper, sugar, mining and metallurgy, urban water supply and drainage, environmental protection, water conservancy, steel, petroleum, pharmaceuticals and other industrial fields to measure various acids , Alkali, salt solution, mud, mineral pulp, paper pulp, coal water slurry, corn steep liquor, fiber pulp, grain pulp, lime milk, sewage, etc.。

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

Electromagnetic flowmeter has a series of excellent characteristics, which can solve the problems that other flowmeters are not easy to use, such as the measurement of dirty flow and corrosive flow.

 

Advantage

The measurement channel is a smooth straight pipe, which will not be blocked, and is suitable for measuring liquid-solid two-phase fluids containing solid particles, such as pulp, mud, sewage, etc.;

The detection will not cause pressure loss, and the energy saving effect is good;

The measured volume flow is actually not significantly affected by changes in fluid density, viscosity, temperature, pressure and conductivity;

Wide range of turndown ratio and wide caliber range;

Corrosive fluids can be used.

 

Disadvantage

Cannot be used to measure gas, steam and liquids containing a large amount of gas;

It cannot be used to measure liquid media with very low conductivity, and the electromagnetic flowmeter cannot measure petroleum products or organic solvents and other media;

It cannot be used to measure high temperature media. At present, it is restricted by the lining material and electrical insulation material of the measuring tube of the electromagnetic flowmeter for general industry;

Electromagnetic flowmeters are easily affected by external electromagnetic interference.

 

Installation Precautions

In order to make the electromagnetic flowmeter meet the working conditions of the measurement site and meet the accuracy and function requirements of the instrument, the following precautions are required during the installation process:


1. Install according to the calibration direction

The direction of the arrow on the sensor must be consistent with the actual flow direction. (If the installation is reversed, the flow direction item in the converter menu must be corrected)


2. Ensure that the full pipe is installed

The full tube measurement state must be ensured, and the non-full tube state cannot occur.

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

Avoid installation upstream of the downward pipeline;

Avoid installing at the highest point of the pipeline, which is easy to collect bubbles;

Instrument knowledge|Precautions for installation of electromagnetic flowmeter

When installing on a horizontal pipeline, the two measuring electrodes should not be directly above and directly below the pipeline. When installed vertically, the fluid should flow from bottom to top.

 

3.Straight pipe distance requirements

Must ensure that the first 10 and rear 5 straight pipe sections.

Instrument knowledge|Precautions for installation of electromagnetic flowmeter


4.Series and parallel installation

If several sensors need to be connected in series on the same pipe in sequence, the distance between each sensor should be at least the length of 2 sensors. If two or more sensors are installed parallel to each other, the distance between the sensors must be greater than 1m.

5. installation and bypass pipe

The pipeline where the flowmeter is installed should have a valve that can cut off the medium in the pipeline to facilitate daily maintenance and maintenance. When the process does not allow flow interruption. A bypass pipe can be added to the pipe where the flowmeter is installed.

6.Sensor ground

The sensor must be well grounded separately


Grounding meaning:

Give the signal source a reference to zero potential, so that the measured medium is connected to the earth. The safety requirements (such as lightning strikes) are against external interference. The grounding point is as close as possible to the sensor, and it must not be connected to the grounding point of other equipment. Ground resistance ≤10Ω

 

Grounding requirements:

Electromagnetic flowmeter transmitter housing, shielded wire, measuring conduit and pipes at both ends of the transmitter must be grounded and set a separate grounding point, and must not be connected to public ground wires or upper and lower pipes such as electric motors; the converter part has passed the cable Line grounding, there is no need to ground again to avoid interference due to different potentials.

 

Grounding method with grounding ring:

If the process pipeline is made of insulating material, it must be equipped with a grounding ring to stabilize the boundary conditions. Improve the measurement qualitative and accuracy.

 

7.Ensure that the split type electromagnetic flowmeter is matched and installed

The split type electromagnetic flowmeter should ensure that the electromagnetic flow converter and the sensor are matched with the number, and the number of the converter and the matching sensor is the same (Zhang Guan Li Dai will not work normally)


8. Wire and lay cables correctly

Must be wired and cabled correctly. The connecting cables of the sensor and the converter must be seated in correct numbers and connected correctly (understand the meaning of each line number)

 

Cable installation precautions: The signal cable and the excitation cable are separated through pipes (iron pipes) to prevent interference and mechanical damage. The special cable provided by the company must be used. The signal cable, excitation cable and power line must be installed separately, and the pulse output line should be considered between the lines. Distributed capacitance should not be too long.

 

9 .Reasonable configuration of the rear position instrument

The rear instrument of the electromagnetic flowmeter must be reasonably configured

The active or passive output should be determined according to the requirements of the subsequent instrument. The external power supply for passive output should meet the technical specifications. If the resistance is connected in series, the resistance value should be within the allowable range.

 

10 .proofreading the power supply voltage

The power supply voltage must be calibrated before commissioning (the phenomenon of 24VDC instrument being burned out by 220VAC power supply is endless)

During debugging, only zero position adjustment is allowed, and various parameters are set after factory calibration without any need to change.

 


Share to
RELATED NEWS / News More
  • Number of clicks: 1001
    2020 - 09 - 24
    Instrument knowledge|Radar level meter, how to reduce the interference in the tank on the measurement When we install the radar level meter, we will encounter many on-site storage tanks with supports, such as beams and brackets,etc . . . These supports will interfere with the signal of the radar level meter. If the above interference objects appear in the radar emission area, when the normal liquid level is below the interference objects, it will inevitably affect the normal measurement of the radar level meter, and false echo signals will appear. When encountering such situations, there are the following solutions: Method 1: Cleaning up on-site interferenceIf the interference is too large, completely occludes or most of the transmission signal of the radar level meter,...
  • Number of clicks: 191
    2020 - 09 - 22
    When selecting the type of radar level gauge, consider the influence of stirring and vacuuming, and pay attention to the power supply and output signal.1. Selection under stirringIn a tank with stirring, guided wave radar is generally not used. The force of stirring can easily bring the cable of the guided wave radar into the propeller, or bend the rod of the guided wave radar. Therefore, only high-frequency or low-frequency horn radar for non-contact measurement can be selected.If the lowest liquid level on site is above the stirring propeller, it generally has no effect on the measurement. If the minimum liquid level will be lower than the stirring propeller, it is necessary to filter out the signal reflected by the propeller by learning the function of false echo, so as to ensure that t...
  • Number of clicks: 3000
    2020 - 09 - 17
    80Ghz FMCW Radar Level meter/ continuous level sensor technical parametersCompared with 26Ghz pulse radar level meter or 6.8Ghz guided wave radar level meter, 80G radar level meter has higher frequency, shorter wavelength, smaller beam angle and more energy concentrated characteristics; coupled with the application of FMCW technology, it has the following characteristics:1.Large range, small blind area;2.The beam angle is small, the antenna size is small, and it is easy to install. Less affected by tank connection size and obstacles;3.The measurement accuracy is high, the anti-interference ability is strong, and the reliability is high. Technical parameter of 80Ghz Radar level meter  Transmit frequency:80GHz;Measuring range:0.1~30/120m;Measurement accuracy:Launch angle:3...
  • Number of clicks: 263
    2020 - 09 - 16
    Intelligent radar water level meter helps carry out flood prevention workRecently, as tropical disturbances in the southern coastal areas of my country have developed into tropical depressions, heavy rainfall has appeared in many areas of southern my country, and the flood control warning has been sounded. Since my country entered the flood season, a new round of flood control and early warning work has once again been put on the agenda. In flood warning work, the status of monitoring instruments can hardly be shaken. In order to do a good job in flood control and early warning, and prevent problems as much as possible, the intelligent radar water level meter DCRD1000A2 researched and developed by Xi'an Dechuang Electrictrical Technology Co., Ltd. not only greatly improves the measurem...
  • Number of clicks: 1001
    2020 - 09 - 10
    Why choose the radar level sensor in industrial process level instruments? The radar level sensor can measure the level that many other level instruments cannot measure, radar level sensor uses the microwave pulse measurement method and can work normally within the specified frequency range. It can be used in environments where inert gases and volatilization exist under the interference of temperature or pressure changes. The radar level sensor is a non-contact continuous measurement type process level instruments, which can be used to measure the level of liquids or solids, particle sizes and particulate materials. It corresponds to 4-20mA output, which is set by inputting the empty tank height E (=zero point), the full tank height F (=full scale) a...
Email:sales@dechuang-auto.com
Adress:
Tel:86-29 88606479
Fax: 86-29 88385903
B203, Gazelle Valley, No.69 Jinye Rd, Hi-tech zone, Xi'an, Shaanxi Province, P.R.China. 710077
Copyright ©2018 - 2019 Dechuang Electrical Technology Co., Ltd SITEMAP
Rhino Cloud Provides Enterprise Cloud Services
犀牛云提供云计算服务