1. Instrument type: 26G high frequency radar level gauge

2. Failure category: F140

3. Failure analysis: F140 means that the echo signal is weak or there is no echo signal.

So, how to solve this problem? The specific operations are as follows:

 

Step 1:Troubleshooting on site

a. Check that the range set by the radar must be greater than the total range of the tank.

b. When the measured medium is liquid, check whether the radar sensor enters water vapor.

When the measured medium is solid, it needs to be checked for crystallization or excessive dust accumulation.

The above cleaning is complete and reinstalled, and then adjust the radar angle until the radar echo signal is the strongest.

 

Step 2: Oscilloscope test and repair

Oscilloscope test no output waveform

1. Firstly, visually check the situation of no missing or missing welding;

2. Use an oscilloscope to check that L1 has no VHD signal input in the middle of the week(Normal see Figure 1)

Maintenance example: troubleshooting and maintenance of radar level gauge F140 

3. Then check that the input pin 4 of the VHD signal output chip U3 has no input (see Figure 2 for normal), check the 4 pin circuit of U3, and find that D9 is open. When replacing it, it is found that D9 is broken. After replacement, the distance measurement is normal.

Maintenance example: troubleshooting and maintenance of radar level gauge F140

 

Any new inquiry about radar level meter, please feel free to contact us!


Share to
RELATED NEWS / News More
  • Number of clicks: 369
    2021 - 07 - 27
    Radar level transmitter are currently widely used in the monitoring of solids, dust particles, liquids, slurries, river water levels, etc. The level signal detected by the radar level transmitter is ultimately connected to the back of our automation control equipment or to the secondary display meter for monitoring control. The specific power supply and communication methods are as follows:1. (4 ~ 20) mA / 24V DC / HART two-wire system2. (4 ~ 20) mA / 24V DC / HART four-wire system3. (4 ~ 20) mA / (85~ 265) V AC / HART four-wire system4. RS485/Modbus/( 6~26)V DC5. Radio frequency 433MThe customer can select the power supply and communication mode according to the actual requirements of the site. If you have any questions, please contact us directly.Xi’an Dechuang Electrical ...
  • Number of clicks: 360
    2021 - 07 - 07
    The screw connection is a widely used detachable fixed connection, which has the advantages of simple structure, reliable connection, and convenient assembly and disassembly. Thread is a key part of thread coupling and screw drive, let us take a look at the classification of thread.According to the tooth shape, it can be divided into triangle, trapezoid, rectangle, zigzag and arc thread;According to the thread rotation direction, it can be divided into left-handed and right-handed;According to the number of spiral lines, it can be divided into single line and multi-line;According to the shape of the thread matrix, it can be divided into cylinder and cone.For threaded connections of radar level transmitters, there are two most common types: G 1 1 / 2A thread; NPT thread.
  • Number of clicks: 321
    2021 - 06 - 29
    The 120GHz FMCW radar level meter successfully applied to the measurement of Chlorinated paraffin in a chemical plant.The working condition is more complicated, the surface foam thickness is about 80cm, the 120GHz radar level meter signal is relatively strong, penetrates the foam, and accurately measures the liquid level.The Main Feature of 120GHz FMCW Radar level meter:1. Not be affected by atmospheric precipitation;2. The ambient temperature is -60°C;3. Being Installed on the outside of tank;4. The antenna inside of the level transmitter is protected by fluoro plastic lens heating;5. The measuring radiation is narrow, easy to install and measurement sensibility;6. The accuracy of the level measurement can't be limited by the temperature of tank;7. Evaporation, Foa...
  • Number of clicks: 0
    2021 - 06 - 25
    Case application I The anti-corrosion radar level meter DCRD1000A5&DCRD1000C5 was successfully applied to a chemical project in Inner Mongolia Since Acid-base solutions are extremely corrosive in industrial production measurement applications, the wetted materials of equipment must be anti-corrosion materials. Our high-frequency radar level meter DCRD1000A5 and guided wave radar level gauge DCRD1000C5 are special models for corrosive conditions. Radar antennas are made of PTFE with good anti-corrosion performance, which has good sealing performance, strong corrosion resistance and stable measurement results.Any inquiry about the radar level meter, welcome to contact us at any time.
  • Number of clicks: 252
    2021 - 06 - 22
    The  Features of DCRD1000C series of Guided Wave Radar Level meter (GWR)The guided wave radar level meter is an excellent level meter with advanced technology, excellent workmanship and high precision. When the guided wave radar level meter is working, an electromagnetic pulse signal is emitted, which is transmitted to the liquid level and returned at a constant speed through a probe or a steel cable, thereby simply and accurately calculating the liquid level height.Guided wave radar level meter are currently used in a wide variety of tank containers. It is used to measure the liquid level or level of medium such as aqueous medium, acidic medium, alkaline medium, oil medium, and particles.The guided wave radar level meter (DCRD1000C series) independently developed by Xi'an Dechuan...
Email:sales@dechuang-auto.com
Adress:
Tel:86-29 88606479
Fax: 86-29 88385903
B203, Gazelle Valley, No.69 Jinye Rd, Hi-tech zone, Xi'an, Shaanxi Province, P.R.China. 710077
Copyright ©2018 - 2019 Dechuang Electrical Technology Co., Ltd SITEMAP
Rhino Cloud Provides Enterprise Cloud Services
犀牛云提供云计算服务