What is the measurement effect of the 120G FMCW radar level gauge? We use the measurement data to prove. The test lasts for 4 days. The radar level gauge measurement data (echo curve and historical curve) are taken every day. The gauge automatically records the historical curve. Through the analysis and judgment of the echo curve and the historical curve, Make sure the radar level gauge is working properly.

The following is a test report of Xi'an Dechuang 120G FMCW continuous wave radar level gauge DCRD1000B in a chemical plant in Guangzhou:

 

 

                                                           120G radar level gauge trial report

 

Address: Guangzhou XXXXX Chemical Co., Ltd.

Purpose: 120G radar level gauge tested under a lot of foam conditions

Content:

1. Instrument parameters and on-site conditions:

Process connection: DN65/PN10; Medium: Chlorinated paraffin

Temperature: 90 °C ; Pressure: <1MPa

Supply voltage: DC24V ; Output: 4-20mA ; Range: 3m

Site conditions:

The working conditions are complicated, and a large amount of steam and foam are generated during the reaction (the foam thickness is up to 800 mm at the highest), and the liquid level fluctuates greatly.

2. Test process data

  The test lasts for 4 days. Every day, the meter measurement data (echo curve and historical curve) are taken. The meter automatically records the historical curve. Through the analysis and judgment of the echo curve and the historical curve, the instrument is guaranteed to work normally. The following is a 4-day meter. Record data.

                                 What is the measurement effect of the 120G FMCW radar level gauge? the measurement data to prove!

Day 1st :


                                  What is the measurement effect of the 120G FMCW radar level gauge? the measurement data to prove!

Day 2nd :

                                  What is the measurement effect of the 120G FMCW radar level gauge? the measurement data to prove!

Day 3rd :

                                  What is the measurement effect of the 120G FMCW radar level gauge? the measurement data to prove!

Day 4th : 

                                What is the measurement effect of the 120G FMCW radar level gauge? the measurement data to prove!

3. Problems

At the beginning of the reactor, a large amount of chlorine gas enters the reactor. At this time, the reaction is intense, and a large amount of foam is generated, which fills the entire reactor. Due to the excessive thickness of the foam (about 800 mm), the echo signal of the meter is weak or There is no echo, which affects the normal measurement of the meter. (Note: This condition is only generated at the beginning of feeding, and will not appear during normal production)

4. Trial results analysis and summary

After four days of on-site test of the instrument, the 120G radar level gauge satisfies the customer's requirements in a large number of foam conditions, solves the problem that many instruments cannot be measured by a large number of foam conditions, and shows that the instrument is in complex conditions. Reliability and stability. At the same time, because the instrument adopts a variety of high-tech technology, the instrument has low installation requirements, quick and easy debugging, and simple maintenance, which has been affirmed by the leadership of the trial company.


Share to
RELATED NEWS / News More
  • Number of clicks: 1001
    2020 - 09 - 24
    Instrument knowledge|Radar level meter, how to reduce the interference in the tank on the measurement When we install the radar level meter, we will encounter many on-site storage tanks with supports, such as beams and brackets,etc . . . These supports will interfere with the signal of the radar level meter. If the above interference objects appear in the radar emission area, when the normal liquid level is below the interference objects, it will inevitably affect the normal measurement of the radar level meter, and false echo signals will appear. When encountering such situations, there are the following solutions: Method 1: Cleaning up on-site interferenceIf the interference is too large, completely occludes or most of the transmission signal of the radar level meter,...
  • Number of clicks: 191
    2020 - 09 - 22
    When selecting the type of radar level gauge, consider the influence of stirring and vacuuming, and pay attention to the power supply and output signal.1. Selection under stirringIn a tank with stirring, guided wave radar is generally not used. The force of stirring can easily bring the cable of the guided wave radar into the propeller, or bend the rod of the guided wave radar. Therefore, only high-frequency or low-frequency horn radar for non-contact measurement can be selected.If the lowest liquid level on site is above the stirring propeller, it generally has no effect on the measurement. If the minimum liquid level will be lower than the stirring propeller, it is necessary to filter out the signal reflected by the propeller by learning the function of false echo, so as to ensure that t...
  • Number of clicks: 3000
    2020 - 09 - 17
    80Ghz FMCW Radar Level meter/ continuous level sensor technical parametersCompared with 26Ghz pulse radar level meter or 6.8Ghz guided wave radar level meter, 80G radar level meter has higher frequency, shorter wavelength, smaller beam angle and more energy concentrated characteristics; coupled with the application of FMCW technology, it has the following characteristics:1.Large range, small blind area;2.The beam angle is small, the antenna size is small, and it is easy to install. Less affected by tank connection size and obstacles;3.The measurement accuracy is high, the anti-interference ability is strong, and the reliability is high. Technical parameter of 80Ghz Radar level meter  Transmit frequency:80GHz;Measuring range:0.1~30/120m;Measurement accuracy:Launch angle:3...
  • Number of clicks: 263
    2020 - 09 - 16
    Intelligent radar water level meter helps carry out flood prevention workRecently, as tropical disturbances in the southern coastal areas of my country have developed into tropical depressions, heavy rainfall has appeared in many areas of southern my country, and the flood control warning has been sounded. Since my country entered the flood season, a new round of flood control and early warning work has once again been put on the agenda. In flood warning work, the status of monitoring instruments can hardly be shaken. In order to do a good job in flood control and early warning, and prevent problems as much as possible, the intelligent radar water level meter DCRD1000A2 researched and developed by Xi'an Dechuang Electrictrical Technology Co., Ltd. not only greatly improves the measurem...
  • Number of clicks: 1001
    2020 - 09 - 10
    Why choose the radar level sensor in industrial process level instruments? The radar level sensor can measure the level that many other level instruments cannot measure, radar level sensor uses the microwave pulse measurement method and can work normally within the specified frequency range. It can be used in environments where inert gases and volatilization exist under the interference of temperature or pressure changes. The radar level sensor is a non-contact continuous measurement type process level instruments, which can be used to measure the level of liquids or solids, particle sizes and particulate materials. It corresponds to 4-20mA output, which is set by inputting the empty tank height E (=zero point), the full tank height F (=full scale) a...
Email:sales@dechuang-auto.com
Adress:
Tel:86-29 88606479
Fax: 86-29 88385903
B203, Gazelle Valley, No.69 Jinye Rd, Hi-tech zone, Xi'an, Shaanxi Province, P.R.China. 710077
Copyright ©2018 - 2019 Dechuang Electrical Technology Co., Ltd SITEMAP
Rhino Cloud Provides Enterprise Cloud Services
犀牛云提供云计算服务