Instrument knowledge| Installation and use of Insertion intelligent electromagnetic flow meter

DATE: 2021-01-14
BROWSE TIMES: 101

 

Instrument knowledge| Installation and use of Insertion intelligent electromagnetic flow meter


There are many types of electromagnetic flow meters, which can be divided into pipeline electromagnetic flow meters and plug-in electromagnetic flow meters according to different installation methods. The plug-in electromagnetic flow meter retains the advantages of the previous pipeline electromagnetic flow meter, but also overcomes the shortcomings of the pipeline electromagnetic flow meter on large-diameter pipelines, such as difficulty in installation, high cost, and difficulty in periodic calibration. It is widely used in tap water, steel and iron. , Petroleum, chemical industry, industry, water conservancy and other sectors of conductive fluids, as well as acid, alkali, salt and other corrosive conductive liquid flow measurement.

Instrument knowledge| Installation and use of Insertion intelligent electromagnetic flow meter

Let us take a look at the plug-in electromagnetic flow meter together.

The basic structure of the plug-in electromagnetic flowmeter is as follows:

 Instrument knowledge| Installation and use of Insertion intelligent electromagnetic flow meter

1. Choice of installation environment

Keep away from equipment with strong electromagnetic fields as much as possible, such as high-power motors, high-power transformers, etc.

There should be no strong vibration at the installation site, the pipes should be firmly fixed, and the ambient temperature should not change too much.

The installation environment should be easy to install and maintain.

2. Choice of installation location

The installation location must ensure that the pipe is always filled with the fluid being tested

Choose a place where the flow of fluid is small, that is, it should be far away from local resistance parts such as pumps, valves, and elbows.

The diameter or circumference of the side tube is easy to measure, and the ellipse should be small.

Avoid measuring negative pressure on site.

When measuring two-phase (solid, liquid, gas, liquid) fluid, the plug-in electromagnetic flowmeter should be selected where it is not easy to cause phase separation.

3 . Opening requirements

There are two straight pipe sections on site: the vertical straight pipe section and the horizontal straight pipe section. Measure the length of the two straight pipe sections. The larger one is preferred;

Try not to have a bypass pipe in the straight pipe section. If there is, the smaller the diameter, the better. There is no bypass pipe preferred.

The installation location is far away from solenoid valves, pumps, frequency converters, and the longest distance is preferred;

Select the straight pipe section, and open holes at the ratio of straight pipe section 3:7, the upstream ratio of the opening is 7 and the downstream ratio is 3, that is, the longer the front straight pipe section of the flowmeter, the better;

Note: The opening position is far away from the solenoid valve, pump, inverter, as the first priority.


4. Welding of the mounting base

The axis of the installation base pipe and the axis of the tested pipe are perpendicular to each other;

Conventional stainless steel flanges are flat welded with stainless steel electrodes, and PVC pipes can be welded with hot melt adhesive tape. After welding, ensure that the flange end face is parallel to the pipe axis, and the welding seam is firm, and can withstand 1.6MPa pressure without leakage;

The opening size of the pipe under test is the same as the outer diameter of the installation base.

5. Sensor installation

The sensor should be installed perpendicular to the measuring pipeline, and the angle between the sensor and the vertical diameter of the pipe section when inserted into the pipeline should be less than 5°. It is suitable for measuring clean media with small vibrations in the pipeline.

There are two ways to insert the sensor: one is to insert it on the central axis of the pipe under test (that is, 1/2 times the pipe diameter); the other is to insert it into the inner wall of the pipe at 1/4 of the pipe.

Turn off the upstream flow control valve or use low-pressure water supply, install the DN50 ball valve on the base, pay attention to the long cavity of the ball valve upwards, check whether the ball valve can be fully opened and fully closed, if there is any problem, repair it. Install the compression threaded seat, compression nut and rubber sealing ring on the ball valve, loosen the positioning screw and compression nut, and insert the sensor insertion rod into the tested pipe through the ball valve. After the insertion depth meets the requirements, tighten the nut and the positioning screw. At the same time, pay attention to the direction of the sensor direction indicator pole to be consistent with the fluid flow.

6.ground

In order to make the meter work reliably, the flow signal generated by the sensor is very weak, usually in the microvolt or millivolt level. Preventing the influence of external electrical interference is an important factor in the good use of the flow meter, and grounding is a very effective measure to solve the impact of electrical interference. Therefore, the sensor should have a good separate grounding wire with a grounding resistance of <10Ω. If the pipeline connecting the sensor is coated with an insulating layer or a non-metallic pipeline, grounding rings or built-in grounding electrodes should be installed on both sides of the sensor.

Grounding method on metal pipe: The inner wall of the metal pipe has no insulating layer, so it is grounded as show below.

Instrument knowledge| Installation and use of Insertion intelligent electromagnetic flow meter

 

Grounding method on plastic pipes or on painted pipes with insulation layer: Grounding rings or built-in grounding electrodes should be installed on both ends of the sensor, so that the measured medium flowing in the pipe is short-circuited with the earth and has zero potential. Otherwise, the electromagnetic flow meter cannot work normally. (See below)

Instrument knowledge| Installation and use of Insertion intelligent electromagnetic flow meter


Share to
RELATED NEWS / News More
  • Number of clicks: 266
    2021 - 03 - 02
    Radar level instruments measure the distance from the transmitter/sensor (located at some high point)to the surface of a process material located further below in much the same way as ultrasonic level sensor, by measuring the time-of -flight of a traveling wave and then determine the level of the process material. They are regarded as continuous level measurement devices because they continue to measure level even as the level of the liquid in the vessel changes.The fundamental difference between a radar level instrument and an ultrasonic level instruments is the type of wave used. Radar level instruments use radio waves instead of sound waves used in ultrasonic instruments. Radio waves are electromagnetic in nature (comprised of alternating electric and magnetic fields), with very high fr...
  • Number of clicks: 2
    2021 - 02 - 25
    The working principle and five precautions for using the radar level sensorThe radar level sensor is a measuring instrument based on the time travel principle. The radar wave runs at the speed of light, and the running time can be converted into a level signal by electronic components. The probe sends out high-frequency pulses and conducts them along the cable and rod probes. When the pulses meet the surface of the material, they are reflected back by the receiver in the meter, and the distance signal is converted into a level signal, Transmit-reflect-receive is the basic working principle of radar level sensor.The antenna of the radar sensor emits electromagnetic wave signals in the form of beams. The emitted waves are reflected on the surface of the material to be measured, and the ...
  • Number of clicks: 212
    2021 - 02 - 23
    Our DCRD1000C series guided wave radar level gauge has been successfully applied to the measurement of liquid level in a horizontal tank of a biotechnology company. Since the product is installed and used, it has monitored the liquid/corrosive liquid level changes in real time, and the signal stability measurement effect is good.If there is similar enquiry, please feel free to contact us!!!
  • Number of clicks: 101
    2021 - 02 - 19
    Factory of Radar level transmitter have resumed production  With the time going by, the Chinese New Year Holiday is over and our factory has resumed production now. The continuous level measuring products include 26GHz high frequency radar level transmitter, guided wave radar level transmitter, 80Ghz FMCW Radar  level transmitter, 120Ghz FMCW Radar level transmitter and Electromagnetic flow meter. These products are widely used in electricity, water, food & beverage, petroleum, petrochemical, coal, chemical, metallurgy industries. Measurable products: petroleum, petroleum products, heavy oil, asphalt, gasoline and other light-colored petroleum products, acid, food, beer, alcohol, milk, liquefied gas, sewage, solution, phenol, ore, cement, seeds, coal ...
  • Number of clicks: 361
    2021 - 02 - 02
    The radar level transmitter should be installed to avoid contact between the sensor and the tank wall and should be kept at a certain distance from the tank wall. Because the radar level transmitter is measured by transmitting high-frequency microwave pulses along the detection component, the dielectric constant changes when these pulse waves encounter the measured medium, causing the emission. Therefore, if the installed radar level transmitter is too close to the tank wall, the dielectric constant of the tank wall may be obtained, which directly leads to the in accuracy of the measured parameters.Correct installation method of radar level transmitter:1. Installed one fourth or sixth of diameter.Note:the minimum distance from the tank wall shall be one tenth ...